XPL2000 |
12 V
|
343.5w/cell |
XPL2000 battery is state-of-art designed with extreme high-rate power output at 5 min-rate, especially for data center backup. The service life is up to 10 years in standby use. |
|
|
|
|
Specification |
|
Capacity |
343.5W @ 5min-rate to 1.60V per cell @25°C (77°F) |
Weight |
Approx. 13.58 Kg (29.94 lbs) |
Maximum Discharge Current |
400A |
Internal Resistance |
Approx. 6.33 mΩ |
Operating Temperature Range |
Discharge:-15℃~50℃ (5°F~122°F) Charge:-15℃~40℃ (5°F~104°F) Storage:-15℃~40℃ (5°F~104°F) |
Nominal Operating Temperature Range |
25°C±3°C(77°F±5°F) |
Float Charging Voltage |
13.5 to 13.8 VDC/Unit Average at 25°C(77°F) |
Recommended Maximum Charging Current Limit |
16.7 A |
Equalization and Cycle Service |
14.4 to 15.0 VDC/Unit Average at 25°C(77°F) |
Self Discharge |
Less than 10% after 90 days, can be stored up to 6 months at 25℃ (77℉) |
Terminal |
I2 thread lead alloy terminal to accept M6 bolt |
Container Material |
ABS(UL94-HB) & Flammability resistance of(UL94-V0) can be available upon request. |
|
|
|